Repository: http://svn.code.sf.net/p/tango-ds/code/DeviceClasses/OtherInstruments/MKS/MKSGE50A
Contact:



Class Description


Tango device server for MKS GE50A mass flow controller

Families: OtherInstruments

Key words:

Platform: Unix Like

Language: Cpp

License: GPL

Contact:

Hardware


Manufacturer: MKS

Product:

Bus: Modbus

Class interface


Attributes:

Name Description
FlowSetPointScalar: DevFloat
FlowScalar: DevFloat
ValvePositionScalar: DevFloat
TemperatureScalar: DevFloat
FlowHoursScalar: DevLong
FlowTotalScalar: DevLong
RampRateScalar: DevLong If value = 0, ramping is disabled. If setting a ramp rate while ramping, the new ramp rate will not take effect until ramping is complete. To disable ramping while in the middle of a ramp, set the ramp rate value to -1.
OpenValveScalar: DevBoolean OpenValve = true and CloseValve = false: open valve OpenValve = false and CloseValve = true: close valve OpenValve = true and CloseValve = true: close valve OpenValve = false and Close Valve = false: controlled by flow setpoint
CloseValveScalar: DevBoolean OpenValve = true and CloseValve = false: open valve OpenValve = false and CloseValve = true: close valve OpenValve = true and CloseValve = true: close valve OpenValve = false and Close Valve = false: controlled by flow setpoint

Commands:

Name Description
StateInput: DevVoid
Output: State
Device state
This command gets the device state (stored in its device_state data member) and returns it to the caller.
StatusInput: DevVoid
Output: ConstDevString
Device status
This command gets the device status (stored in its device_status data member) and returns it to the caller.
ResetInput: DevVoid
Output: DevVoid
Will reset the device’s set point to zero and place the valve state to “controlled by flow set point”, i.e. OpenValve = 0, Close Valve = 0
FlowZeroInput: DevVoid
Output: DevVoid
Sets flow to zero.

Pipes:

Properties:

Name Description
HostNameDevString Hostname / Ip address of device
PortNumberDevString Modbus tcp port number, defaults to 502