This is historical information of device classes implemented in StanfordDG645 device server.

Use this link to find the valid information.

Development status: Released
Information status: Updated

Contact:



Class Description


Device server for a single delay channel.

Families: CounterTimer

Key words:

Platform: Unix Like

Language: Cpp

License: GPL

Contact:

Hardware


Manufacturer: Stanford Research Systems

Product:

DG645

Bus: Ethernet

Class interface


Attributes:

Name Description
OutputAmplitudeScalar: DevFloat The amplitude for the output. It might be positive or negative and has to be in the range between 0.5V and 5V. The absolute level may not exceed 6V.
OutputOffsetScalar: DevFloat The DC offset for the output. It has to be in the range between -2V and 2V. The absolute level may not exceed 6V.
OutputWidthScalar: DevDouble The pulse width for the output.
TriggerDelayScalar: DevDouble The delay between t0 and the trigger of the channel.

Commands:

Name Description
StateInput: DevVoid
Output: State
Device state
This command gets the device state (stored in its device_state data member) and returns it to the caller.
StatusInput: DevVoid
Output: ConstDevString
Device status
This command gets the device status (stored in its device_status data member) and returns it to the caller.

Pipes:

Properties:

Name Description
ControlDevicePathDevString Path to the StanfordDG645Control device providing the connection.
ChannelDevUShort Channel number from 0-4 to be controlled by this device. They are mapped as follows: 0 - t0, 1 - AB, 2 - CD, 3 - EF, 4 - GH.

26 Sep 2020, DS Admin
Updated:
A device class has been added.
You are looking at this version now.



26 Sep 2020, DS Admin
Updated:
The device class has been updated.
You can see previous version here .



26 Jan 2019, DS Admin
Updated:
A device class has been added.
You can see previous version here .



26 Jan 2019, DS Admin
Created:
The device class has been added to catalogue.
Added by:dadmin on:26 Sep 2020, 3:27 a.m.