Xbpm - - TANGO Controls

This is historical information of device classes implemented in Xbpm device server.

Use this link to find the valid information.

Development status: New development
Information status: Updated

Contact:



Class Description


This class is an universal Xbpm controller.
Xpbm Currents (mA) and Beam Position X (�m) and Z (�m) will be processed by this class.

Families: BeamDiagnostics

Key words: BeamDiag

Platform: All Platforms

Language: Cpp

License:

Contact:

Hardware


Manufacturer: none

Bus: Not Applicable

Class interface


Attributes:

Name Description
gainScalar: DevDouble —
enableAutoRangeScalar: DevBoolean —
current1Scalar: DevDouble —
current2Scalar: DevDouble —
current3Scalar: DevDouble —
current4Scalar: DevDouble —
intensityScalar: DevDouble —
measurementUnitScalar: DevString —
horizontalPositionScalar: DevDouble —
verticalPositionScalar: DevDouble —
computationModeScalar: DevUShort —

Commands:

Name Description
SetUnitInput: DevUShort
Output: DevVoid
Sets currents unit.
StateInput: DevVoid
Output: State
This command gets the device state (stored in its device_state data member) and returns it to the caller.
StatusInput: DevVoid
Output: DevString
This command gets the device status (stored in its device_status data member) and returns it to the caller.
StartInput: DevVoid
Output: DevVoid
Starts acquisition in continuous mode.
StopInput: DevVoid
Output: DevVoid
Stops acquisition

Pipes:

Properties:

Name Description
ElectrometerProxyNameDevString Name of the Electrometer Device proxy (ex : LoCum-4 Device).
ElectrometerGainNameDevString Name of the Electrometer Device gain attribute (ex: gain).
SaiControllerProxyNameDevString Name of the SaiController Device proxy.
SaiControllerChan0NameDevString Name of the SaiController channel 0 attribute (ex: channel0).
SaiControllerChan1NameDevString Name of the SaiController channel 1 attribute (ex: channel1).
SaiControllerChan2NameDevString Name of the SaiController channel 2 attribute (ex: channel2).
SaiControllerChan3NameDevString Name of the SaiController channel 3 attribute (ex: channel3).
I1OffsetDevDouble Current offset (in �A) on electrode 1.
I2OffsetDevDouble Current offset (in �A) on electrode 2.
I3OffsetDevDouble Current offset (in �A) on electrode 3.
I4OffsetDevDouble Current offset (in �A) on electrode 4.
GI1DevDouble Gain correction (in �A/V) for electrode 1.
GI2DevDouble Gain correction (in �A/V) for electrode 2.
GI3DevDouble Gain correction (in �A/V) for electrode 3.
GI4DevDouble Gain correction (in �A/V) for electrode 4.
V1OffsetDevDouble Voltage offset (in V) on electrode 1.
V2OffsetDevDouble Voltage offset (in V) on electrode 2.
V3OffsetDevDouble Voltage offset (in V) on electrode 3.
V4OffsetDevDouble Voltage offset (in V) on electrode 4.
LowVoltageThresholdDevDouble If the input voltage of the ADC decrease this threshold (in V), the corresponding average current attribute become ALARM (i.e. if |Vmes| < threshold).
HighVoltageThresholdDevDouble If the input voltage of the ADC exceed this threshold (in V), the corresponding average current attribute become ALARM (i.e. |Vmes|> threshold).
IntensityThresholdDevDouble Current out of which the Measured Intensity has a meaning (in micro-A).
StartAtInitDevBoolean Launch start command at initialization time.
EnableSigmaIntensityDevBoolean Enables or disables standard deviation intensity computing (standardDeviationIntensity & currentSpectrum attributes).
EnablePositionHistoryDevBoolean Enables or disables standard deviation position computing (standardDeviationPosition & historyPosition attributes)
EnableIntensityHistoryDevBoolean Enables or disables intensity history (historyIntensity attribute)
EnableFluxComputingDevBoolean Enables or disables beam flux display (flux attribute).
BeamEnergyProxyNameDevString Name of the beam Energy Device Proxy.
EnergyAttrDevString Name of the energy attribute to read from the beam energy Device Proxy.
ModeXString[]Type List of the properties needed by the computation mode `X`. Format: {key}::{value}
ScanModeDevBoolean If true, this property enables the scan mode, i.e. the polling task is disabled and data is computed on each client`s request.
XbpmTypeDevString XBPM type among PSD, Quadrant. Determines the intensity calculation.

22 Feb 2018, DS Admin
Updated:
The device class has been updated.
You are looking at this version now.



22 Feb 2018, DS Admin
Updated:
The device class has been updated.
You can see previous version here .



20 Apr 2017, Piotr Goryl
Updated:
The device class has been updated.
You can see previous version here .



23 Feb 2017, Piotr Goryl
Created:
The device class has been added to catalogue.
Added by:pgoryl2 on:22 Feb 2018, 2:45 p.m.