MOSTAB - - TANGO Controls

This is historical information of device classes implemented in MOSTAB device server.

Use this link to find the valid information.

Development status: Released, Release: release_1_0_4
Information status: Updated
Repository: http://svn.code.sf.net/p/tango-ds/code/DeviceClasses/BeamlineComponents/MOSTAB
Contact:



Class Description


This device controls the MOSTAB SIS2900-LVPZT system designed by STRUCK. it uses

a RS232 communication. a right wire is needed. the communication parameters are: - baud rate = 9600 - stop bit = 1 - parity = none - 8 data bits. Each frame has to be terminated by "LF" and "CR" characters (10 and 13 in decimal notation) frame exemples : - to return read only parameters : � RG � + LF + CR - to set the loop gain � S2=12.125 � + LF + CR

5 run modes are available: - 0 means " manual " - 1 means " Peak Search " - 2 means " Peak Hold " - 3 means " standby " - 4 means " Track set point " To change the run mode, use the SetRunMode(code) command and choose the corresponding number code

Families: BeamlineComponents

Key words:

Language: Cpp

License:

Contact:

Class interface


Attributes:

Name Description
beamLineNumberScalar: DevShort —
setPointScalar: DevDouble —
input0Scalar: DevDouble —
input1Scalar: DevDouble —
i0OverI1Scalar: DevDouble —
outputScalar: DevDouble —
deltaScalar: DevDouble —
sigmaScalar: DevDouble —
pidGainScalar: DevDouble —
pidIntegralPartScalar: DevDouble —
pidDifferentialPartScalar: DevDouble —
modulationFrequencyScalar: DevDouble —
lowPassFilterScalar: DevDouble —
minOutputVoltageScalar: DevDouble —
maxOutputVoltageScalar: DevDouble —
twoInputsScalar: DevBoolean —

Commands:

Name Description
StateInput: DevVoid
Output: State
This command gets the device state (stored in its device_state data member) and returns it to the caller.
StatusInput: DevVoid
Output: DevString
This command gets the device status (stored in its device_status data member) and returns it to the caller.
SetRunModeInput: DevShort
Output: DevVoid
5 run modes are available: - 0 means " manual " - 1 means " Peak Search " - 2 means " Peak Hold " - 3 means " standby " - 4 means " Track set point "
SendMostabCommandInput: DevString
Output: DevString
to send MOSTAB commands
SaveInput: DevVoid
Output: DevVoid
store current parameter set (mostab command: "U")
ReloadInput: DevVoid
Output: DevVoid
Load default parameters (mostab command: "D")

Pipes:

Properties:

Name Description
SerialDeviceProxyNameDevString Name of the Serial device server proxy which communicates with the MOSTAB device

22 Feb 2018, DS Admin
Updated:
The device class has been updated.
You are looking at this version now.



20 Apr 2017, Piotr Goryl
Updated:
The device class has been updated.
You can see previous version here .



23 Feb 2017, Piotr Goryl
Created:
The device class has been added to catalogue.
Added by:pgoryl2 on:22 Feb 2018, 2:23 p.m.