Average: 0
Rating Count: 0

Development status: New development
Information status: Updated
Repository: http://svn.code.sf.net/p/tango-ds/code/DeviceClasses/Communication/OPCaccess
Contact:



Class Description


The OPCaccess class maps data items from an OPC server to Tango

attributes. For every OPCaccess device the attibute data type has to be specified. Tango can handle only double, long and short attributes. All OPC data items are casted to the requested data type. If an OPC item is an array (uses the ,lxx) extension in the item name, the tango attribute is created as a spectrum attibute.

For OPC servers which cannot handle array types, the property "array_handling" must be set to false to trigger correct data conversion.

Families: Communication

Key words:

Language: Cpp

License:

Contact:

Class interface


Attributes:

Commands:

Name Description
ReadDirectInput: DevVoid
Output: DevVoid
Triggers reading of data directly from the OPC item.
ReadCacheInput: DevVoid
Output: DevVoid
Triggers reading of data from the OPC data cache.
StatusInput: DevVoid
Output: DevString
This command gets the device status (stored in its device_status data member) and returns it to the caller.
StateInput: DevVoid
Output: State
This command gets the device state (stored in its device_state data member) and returns it to the caller.

Pipes:

Properties:

Name Description
Array_handlingDevString Specifies whether the OPC server used is capable to handle arrays or only scalar data types. array_handling = ``true`` , array data types are handled. array_handling = ``false``, only scalar data types are handled.
Data_typeDevString This is set as the requested data type for the OPC items to be read. The possible data types are ``double``, ``long`` or ``short``.
Item_namesString[]Type Specifies the OPC item names to be read from the OPC server via the given path.
Path_nameDevString Specifies the path of the OPC item to be addressed on the OPC server.
Server_nameDevString Specifies the name of the OPC server to be used.
DataFromCacheDevShort Triggers data reading from the OPC cache or directly from the OPC item. Set to 1 -> cache reading is enabled. Set to 0 -> direct access is enabled.


Please log in to comment.

22 Feb 2018, DS Admin
Updated:
The device class has been updated.
You can see previous version here .



20 Apr 2017, Piotr Goryl
Updated:
The device class has been updated.
You can see previous version here .



23 Feb 2017, Piotr Goryl
Created:
The device class has been added to catalogue.
Added by:pgoryl2 on:23 Feb 2017, 10:52 a.m.