This device server is certified as a reference implementation.

Average: 0
Rating Count: 0

Development status: Released
Information status: Updated
Repository: https://github.com/tango-controls/starter
Contact:



Class Description


This device server is able to control <b>Tango</b> components (database, device servers, clients...). It is able to start or stop and to report the status of these components.

Families: System

Key words:

Platform: All Platforms

Language: Cpp

License: GPL

Contact:

Hardware


Manufacturer: ESRF

Bus: Not Applicable

Class interface


Attributes:

Name Description
NotifdStateScalar: DevState return ON or FAULT if notify daemon is running or not.
HostStateScalar: DevShort
RunningServersSpectrum: DevString
StoppedServersSpectrum: DevString Return all the Stopped servers.\n
ServersSpectrum: DevString Return all registred servers for this host.\nServer names are followed by their states and controls

Commands:

Name Description
ResetStatisticsInput: DevVoid
Output: DevVoid
Reset statistics file.
StateInput: DevVoid
Output: State
State Code
This command gets the device state (stored in its <i>device_state</i> data member) and returns it to the caller.
StatusInput: DevVoid
Output: ConstDevString
Status description
This command gets the device status (stored in its <i>device_status</i> data member) and returns it to the caller.
DevStartInput: DevString
Server to be started.
Output: DevVoid
Start the specified server.
DevStopInput: DevString
Servero be stopped.
Output: DevVoid
Stop the specified server.
DevStartAllInput: DevShort
Startup level.
Output: DevVoid
Start all device servers controled on the host for the argin level.
DevStopAllInput: DevShort
Startup Level.
Output: DevVoid
Stop all device servers controled on the host for the argin level.
DevGetRunningServersInput: DevBoolean
True for all servers. False for controled servers only.
Output: DevVarStringArray
List of the processes which are running.
Control the running process from property list. And return the list of the processes which are really running.
DevGetStopServersInput: DevBoolean
True for all servers. False for controled servers only.
Output: DevVarStringArray
List of the processes which are not running.
Control the running process from property list. And return the list of the processes which are not running.
DevReadLogInput: DevString
server name and domain (e.g. Starter/corvus) If argin ==``Starter`` -> return Starter logg file content. If argin ==``Statistics`` -> return Starter statistics file content.
Output: ConstDevString
String found in log file.
At server startup, its standard error is redirected to a log file. This command will read this file and return the read string from the file.
HardKillServerInput: DevString
Server name
Output: DevVoid
Hard kill a server (kill -9)
NotifyDaemonStateInput: DevVoid
Output: State
Tango::ON if Notify daemon is running else Tango::FAULT.
Returns the Notify Daemon state.
UpdateServersInfoInput: DevVoid
Output: DevVoid
Indicate to the device server than the information about servers to be controlled has been modified. The device server must read the database to update the servers info list. If the default case, this command is sent by Database server itself.

Pipes:

Properties:

Name Description
AutoRestartDurationDevLong If this property is greater than 0, if a server has been running more than the specified value (in minutes), and has failed, it will be restart automaticly.
InterStartupLevelWaitDevLong Time to wait before two startup levels in seconds.
KeepLogFilesDevLong Number of log file kept.
LogFileHomeDevString The home directory to log servers traces. For Linux the default value is /var/tmp For Win32 it is c:\temp
ServerStartupTimeoutDevLong Timeout on device server startup in seconds.
StartDsPathArray of DevString Path to find executable files to start device servers
StartServersAtStartupDevBoolean Skip starting servers at startup if false.
UseEventsDevShort Use events if not null.
WaitForDriverStartupDevShort The Starter will wait a bit before starting servers, to be sure than the drivers are started.This time is in seconds.
AutoRestartDurationDevLong If this property is greater than 0, if a server has been running more than the specified value (in minutes), and has failed, it will be restart automaticly.
LogFileHomeDevString The home directory to log servers traces. For Linux the default value is /var/tmp For Win32 it is c:\temp
NbStartupLevelsDevShort Number of startup levels managed by starter.
ReadInfoDbPeriodDevShort Period to read database for new info if not fired from Database server.
ServerStartupTimeoutDevLong Timeout on device server startup in seconds.
StartServersAtStartupDevBoolean Skip starting servers at startup if false. It a way to do not have a big re-start of many servers after a power cut.
UseEventsDevShort Use events if not null.


Please log in to comment.

5 Jan 2017, Andy Gotz
Updated:
The device server has been updated.
You can see previous version here .



5 Jan 2017, Andy Gotz
Created:
The device server has been added to catalogue.
Added by:agotz on:5 Jan 2017, 3:33 p.m.