Development status:
Released,
Release: 1.0
Information status: New
Repository:
https://github.com/gerard-af/tango-controls-wiener-mpod-server
Contact:
Class Description
Device Server controlling the Wiener MPOD and it`s power modules such as - Wiener LV power supplies - iseg HV power supplies
It contains low level access functions for directly accessing the SNMP protocol. These functions are named snmp....
It also contains high level access functions for controlling:
- the crate functionality. The functions are named crate....
The crateGet... functions don`t take arguments. The crateSet... functions need the new value as argument.
- the module functionality. The functions are named module....
The moduleGet... functions need the slot_index as argument. The moduleSet... functions need the slot_index and the new value as argument.
- the channel functionality. The functions are named channel....
The channelGet... functions need the slot_index and the channel_index as arguments. The channelSet... functions need the slot_index, the channel_index and new value as arguments.
- the group functionality. The functions are named group....
The groupGet... functions requires the group_index as argument. The groupSet... functions need the group_index ant the new value as argument.
Further information can be found on the manufacturer`s web sites and in the user manuals for MPOD and the inserted modules.
Families: PowerSupply
Key words: iseg,EHS
Platform: Unix Like
Language: Cpp
License: GPL
Contact:
Hardware
Manufacturer: Wiener
Product:
MpodC
Bus: Ethernet
Class interface
Attributes:
Name | Description |
---|---|
NumberOfGroupsScalar: DevULong | The number of groups defined for HV and LV channels. Requires that thecrate has been switched on. |
NumberOfChannelsScalar: DevULong | The number of detected HV and LV channels. Requires that the crate has been switched on. |
NumberOfModulesScalar: DevULong | The number of modules inserted and recognized. This is only valid when the crate has been switched on. |
FanSpeedScalar: DevULong | The crate`s fan speed. For most crates the allowed values are 0 or 1200 - 5000. |
SerialNumberScalar: DevString | The crate's serial number. |
SysStatusAsStringScalar: DevString | The crate`s status as string. Only the most important flag of SysStatus is reported. |
SysStatusScalar: DevULong | The crate`s status. Possible values are: mainOn (0) , mainInhibit (1) , localControlOnly (2) , inputFailure (3) , outputFailure (4) , fantrayFailure (5) , sensorFailure (6), vmeSysfail (7), plugAndPlayIncompatible (8), busReset (9), supplyDerating (10), supplyFailure (11), supplyDerating2 (12), supplyFailure2 (13) |
SysMainSwitchScalar: DevULong | The crate`s main switch. Possible values are 0 (off) or 1 (on). |
SysDescrScalar: DevString | The system description. This string also contains the firmware version. |
IsMibFileLoadedScalar: DevBoolean | This value is set when th device server is initialized. It is true if the file WIENER-CRATE-MIB.txt was found. The functionality of the device server will be restricted without this file. |
Commands:
Name | Description |
---|---|
ChannelGetMeasurementTimeVectorInput: DevVoid Output: DevVarDoubleArray |
— |
ChannelGetMeasurementTerminalVoltageVectorInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevVarDoubleArray |
— |
ChannelGetMeasurementSenseVoltageVectorInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevVarDoubleArray |
— |
ChannelGetMeasurementCurrentVectorInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevVarDoubleArray |
— |
SnmpTranslateToOIDInput: DevString Human readable string Output: DevString OID as string |
Inverses TranslateFromOID. |
SnmpTranslateFromOIDInput: DevString OID as string Output: DevString Human readable string |
For a given OID variable the human readable form of the variable is returned such as defined in the file WIENER-CRATE-MIB.txt |
SnmpSetValueIntInput: DevVarLongStringArray Variable name and value to set Output: DevBoolean True on success, false otherwise. |
Set a SNMP variable defined by an OID to the integer value passed as an argument. |
SnmpSetValueDoubleInput: DevVarDoubleStringArray Variable name (string) and value to set (double). Output: DevBoolean True on success, false otherwise. |
Set a SNMP variable defined by an OID to the double value passed as an argument. |
SnmpGetValueStringInput: DevString OID name Output: DevString String variable value |
Reads the SNMP variable defined by an OID or an equivalent human readable string. Returns a string value. |
SnmpGetValueIntInput: DevString OID name Output: DevLong |
Reads the SNMP variable defined by an OID or an equivalent human readable string. Returns an unsigned integer value. |
SnmpGetValueDoubleInput: DevString OID name Output: DevDouble Double value |
Reads the SNMP variable defined by an OID or an equivalent human readable string. Returns a double value. |
SnmpGetNextOIDInput: DevString CurrentOID Output: DevString NextOID |
For a given OID variable the next OID is returned. Rhis allows to iterate over all OIDs exposed by the MPOD controler. This is mostly a debug function. It can be used to implement a functionality similar to ``snmpwalk``. |
SnmpGetDescriptionInput: DevString OID as string Output: DevString Description from MIB file. |
This function simplifies debugging when working with the low level snmp functions. It returns a description for a given OID or the corresponding human readable string. |
ModuleSetRampSpeedVoltageInput: DevVarDoubleArray Slot index, Value Output: DevBoolean |
— |
ModuleSetRampSpeedCurrentInput: DevVarDoubleArray Slot index, Value Output: DevBoolean |
— |
ModuleSetDoClearInput: DevVarULongArray Slot index, Value Output: DevBoolean |
— |
ModuleGetStatusAsStringInput: DevLong Slot index Output: DevString |
— |
ModuleGetStatusInput: DevLong Slot index Output: DevLong |
— |
ModuleGetRampSpeedVoltageInput: DevLong Slot index Output: DevDouble |
— |
ModuleGetRampSpeedCurrentInput: DevLong Slot index Output: DevDouble |
— |
ModuleGetNumberOfChannelsInput: DevLong Slot index Output: DevLong |
This command returns the number of channels for the module in slot `slot index`. |
ModuleGetMeasurementTemperature3Input: DevLong Slot index Output: DevDouble |
— |
ModuleGetMeasurementTemperature2Input: DevLong Slot index Output: DevDouble |
— |
ModuleGetMeasurementTemperature1Input: DevLong Slot index Output: DevDouble |
— |
ModuleGetMeasurementTemperature0Input: DevLong Slot index Output: DevDouble |
— |
ModuleGetIsHvModuleInput: DevLong Slot index Output: DevBoolean |
This command returns true if the module in `slot index` is a HV module. |
ModuleGetIndexInput: DevLong Slot index Output: DevLong |
— |
ModuleGetHardwareLimitVoltageInput: DevLong Slot index Output: DevDouble |
— |
ModuleGetHardwareLimitCurrentInput: DevLong Slot index Output: DevDouble |
— |
ModuleGetEventStatusAsStringInput: DevLong Slot index Output: DevString |
— |
ModuleGetEventStatusInput: DevLong Slot index Output: DevLong |
— |
ModuleGetEventChannelStatusInput: DevLong Slot index Output: DevLong |
— |
ModuleGetDescriptionInput: DevLong Slot index Output: DevString |
— |
ModuleGetAuxiliaryMeasurementVoltage1Input: DevLong Slot index Output: DevDouble |
— |
ModuleGetAuxiliaryMeasurementVoltage0Input: DevLong Slot index Output: DevDouble |
— |
GroupSetSwitchInput: DevVarULongArray Group index, Value Output: DevBoolean |
— |
GroupGetIndexInput: DevLong Group index Output: DevLong |
— |
CrateSetSysMainSwitchInput: DevULong Value Output: DevBoolean |
— |
CrateSetSysHardwareResetInput: DevULong Value Output: DevBoolean |
— |
CrateSetFanSpeedInput: DevLong Value Output: DevBoolean |
— |
CrateGetSysStatusAsStringInput: DevVoid Output: DevString |
— |
CrateGetSysStatusInput: DevVoid Output: DevLong |
— |
CrateGetSysMainSwitchInput: DevVoid Output: DevLong |
— |
CrateGetSysDescrInput: DevVoid Output: DevString |
— |
CrateGetSerialNumberInput: DevVoid Output: DevString |
— |
CrateGetOccupiedSlotsInput: DevVoid Value Output: DevVarULongArray |
Returns the slot indices of the slots occupied by a HV or a LV module. |
CrateGetNumberOfModulesInput: DevVoid Output: DevLong |
— |
StateInput: DevVoid Output: State State Code |
This command gets the device state (stored in its <i>device_state</i> data member) and returns it to the caller. |
CrateGetNumberOfGroupsInput: DevVoid Output: DevLong |
— |
CrateGetNumberOfChannelsInput: DevVoid Output: DevLong |
— |
CrateGetFanSpeedInput: DevVoid Output: DevLong |
— |
ChannelSetVoltageRiseRateInput: DevVarDoubleArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetVoltageFallRateInput: DevVarDoubleArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetVoltageInput: DevVarDoubleArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetUserConfigInput: DevVarULongArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetTripTimeInput: DevVarULongArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetSwitchInput: DevVarULongArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetSupervisionMinSenseVoltageInput: DevVarDoubleArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetSupervisionMaxTerminalVoltageInput: DevVarDoubleArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetSupervisionMaxCurrentInput: DevVarDoubleArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetSupervisionBehaviorInput: DevVarULongArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetCurrentRiseRateInput: DevVarDoubleArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetCurrentFallRateInput: DevVarDoubleArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelSetCurrentInput: DevVarDoubleArray ModuleSlotIndex, ChannelIndex, Value Output: DevBoolean |
— |
ChannelGetVoltageRiseRateInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetVoltageFallRateInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetVoltageInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetUserConfigInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevLong |
— |
ChannelGetTripTimeInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevLong |
— |
ChannelGetSwitchInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevLong |
— |
ChannelGetSupervisionMinSenseVoltageInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetSupervisionMaxTerminalVoltageInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetSupervisionMaxPowerInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetSupervisionMaxCurrentInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetSupervisionBehaviorInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevLong |
— |
ChannelGetStatusAsStringInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevString |
— |
ChannelGetStatusInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevLong ChannelStatus |
Return the channel status as integer for a given module slot and channel index. |
ChannelGetMeasurementTerminalVoltageInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetMeasurementTemperatureInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetMeasurementSenseVoltageInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetMeasurementCurrentInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetIndexInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevLong |
— |
ChannelGetCurrentRiseRateInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetCurrentFallRateInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetCurrentInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble Output current or trip current (HV). |
Returns the output current for the specified channel. It this current is reached, the channel operates in current regulation mode. The corresponding flag is set in the channel status. If current trips are enbled for HV modules, the returned current defines the trip current. |
ChannelGetConfigMaxTerminalVoltageInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetConfigMaxSenseVoltageInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
ChannelGetConfigMaxCurrentInput: DevVarULongArray ModuleSlotIndex, ChannelIndex Output: DevDouble |
— |
StatusInput: DevVoid Output: ConstDevString Status description |
This command gets the device status (stored in its <i>device_status</i> data member) and returns it to the caller. |
Pipes:
Properties:
Name | Description |
---|---|
ThreadPollingIntervalMsSlowDevULong | Like ThreadPollingIntervalMsFast. The property ThreadPollingIntervalMsSlow concerns the polling of SNMP variables that are set by the user. These variables are read if ThreadPollingIntervalMsSlow has expired or a value has been set. This represents an important speedup for the communication with the MPOD. |
ThreadPollingIntervalMsIntermediateDevULong | Like ThreadPollingIntervalMsFast. The property ThreadPollingIntervalMsIntermediate concerns the polling for status flags and most other SNMP variables. |
ThreadPollingIntervalMsFastDevULong | The communication to the MPOD can be run in a thread. This property defines a time intarval for periodic polling of all data in milliseconds. The defined interval should be 200 ms or greater. If the value of this property is 0, the thread is not started, all commands are directly sent to the MPOD, the device server waits for the response from the MPOD. The property ThreadPollingIntervalMsFast concerns the measured voltages and currents. |
SnmpTimeoutDevLong | This value is passed to the net-snmp library. For values <= 0 the library default is used. The value is given in ms. Appropriate values are 500 ... 2000. |
SnmpCommunityNameDevString | Used SNMP community. This property can limit the access to SNMP variables. By default `guru` defines the read-write community. The community `public` prohibits write operations. These default settings can be changed. |
IpAddrDevString | IP Address for the MPOD controller. |
Please log in to comment.
README
# tango-controls-wiener-mpod-server
[Tango controls](http://www.tango-controls.org/) device servers for controlling a [Wiener](http://www.wiener-d.com/) MPOD crate and inserted high- or low-voltage modules.
# WienerMpodLvHvCtrl
This is the main device server class. It makes use of the [net-snmp](http://www.net-snmp.org/) library to communicate with the MPOD over a network connection.
The SNMP crate variables are available as attributes.
The module and channel SNMP variables can be accessed over functions.
See the README.txt file in the WienerMpodLvHvCtrl directory for information about compilation.
The included html documentation gives further details about the device server configuration and the exposed functions and attributes.
The DS configuration is also illustrated in the [wiki](https://github.com/gerard-af/tango-controls-wiener-mpod-server/wiki).
The DS might not run if your MPOD controller runs old firmware. We tested version MPOD 2.1.2212.0 and everything was fine. If your version is older a firmware update might be necessary.
# WienerMpodHvModule
This device class simplifies working with a single Iseg high-voltage modules by exposing the module's and the channels' SNMP
variables as attributes. The channel attributes are generated dynamically for a given number of channels.
It requires a running WienerMpodLvHvCtrl device server.
See the README.txt file in the WienerMpodHvModule directory for information about compilation.
The included html documentation gives further details about the device server configuration and the exposed attributes.
The DS configuration is also illustrated in the [wiki](https://github.com/gerard-af/tango-controls-wiener-mpod-server/wiki).
# Other Software
Other software for controlling MPOD crates is available. Using this software will familiarize you with your MPOD crate and help you to optimize your Tango-controls setup. You can also run this control software in parallel with you Tango setup.
* Easy LV|HV is available from the [Analog Flavor website](http://www.analogflavor.com/en/bespice/easy-lvhv-control-software/).
* iseg SNMPcontrol can be downloaded from the [iseg support page](https://iseg-hv.com/en/support/downloads).
# Support
* contact [Physical Instruments](https://www.physical-instruments.fr/) for support in France.
* contact [Analog Flavor](http://www.analogflavor.com/) for international support.
# Further Information
* the WIENER-CRATE-MIB.txt file from the [Wiener website](http://www.wiener-d.com/) explains all used SNMP variables in details.
* the MPOD manual from the [Wiener website](http://www.wiener-d.com/) explains how to use an MPOD.
* the user guide of your [Iseg](http://iseg-hv.com) module explains how to use your high-voltage module.
Created:
The device class has been added to catalogue.